Máy dò khí cố định
XNX™ Universal Transmitter Fixed Gas Detectors
Gas Type: Flammable; CO2; O2; H2S; CO; SO2; NH3; CL2; ClO2; NO; NO2; H2; HF; PH3; CH4; HC
Certificate: Atex, UL, cUL, IECEx
Material: LM25 Aluminum, Painted SS316
The XNX Universal Transmitter is a comprehensive solution designed to operate in hazardous locations and utilize sensor technologies to detect toxic or flammable and oxygen depletion gas hazards using infrared, catalytic bead or electrochemical-based sensors.
This specification details the operating characteristics and features of the XNX Universal transmitter.
Gas Type:O2 (0-25%), H2S (0-50ppm or 0-500ppm), CO ( 0-1000ppm), SO2 (0-20ppm or 0-50ppm), NH3 (0-200ppm or 0-1000ppm), Cl2 (0-20ppm or 0-1ppm), NO (0-100ppm), NO2 (0-50ppm), H2 (0-1000ppm or 0-10000ppm), HCL (0-20ppm), HF (0-12ppm), O3 (0-0.4ppm), PH3 (0-1.2ppm), CO2 (0-5% Vol), CH4 (0-5%Vol or 0-100% LEL), Flammable (0-100%LEL)
Compatible with full range of HA sensor technologies: Catalytic, Electrochemical Cell và IR
Material: LM25 Aluminum, Painted ( Stainless Stell SS316)
Sigmal: 4-20mA (Sink, source), with HART® as standard, Modbus, Relay (option)
Signal Accuracy: +/- 1% FS
Temperatue: -400C to + 650C
Humidity: 20% to 90%
IP: NEMA 4X IP65
Power Supply: 18VDC – 32 VDC
Hazardous Area Certificate: ATEX: Ex II 2 G D, EEx [ia] IIC T5 (Tamb -40°C to +65°C) UL: Class I, Div 1, Groups B, C, and D / Class 1, Zone 1 AEx d IIC T5 (Tamb -40°C to +65°C) CSA: Class I, Div 1, Groups B, C, and D T5 (Tamb -40°C to +65°C)
SIL Level: SIL 2
User interface: Standard Custom Backlit LCD 2.5” High Resolution Dot Matrix Display with three colour Red, Yellow, Green
Self-test and fault indication features
Title | Size | Download |
---|---|---|
DATASHEET XNX ™ | 2.77 MB | Download |